Logo

MonoCalc

/

Transformer Turns Ratio Calculator

Physics

What are you solving for?

One set of entries feeds every panel, so the ratio, the voltage and current columns, the VA balance and the winding diagram all describe the same transformer. Switching mode keeps what you have already typed.

V_s = V_p × N_s / N_p

The everyday question: a known mains primary, a known pair of windings, and the output voltage that results. The current and VA columns fill in as soon as you give a load.

The classic European mains transformer: 1150 turns against 60, a 19.167:1 step-down, 60 VA.
How the headline ratio is written — n:1, 1:n, a bare decimal or reduced whole turns.
0 to 10; also used by the copy and download buttons.

The windings

A whole number of at least 1. Leave it blank and the ratio still comes from the voltages.
The output winding. Np ÷ Ns is the turns ratio n.
The RMS voltage applied to the primary — 230 V or 120 V for mains work.

Load, power and efficiency

Everything here is optional. Give one current and the other follows from the ratio; give a load impedance and the reflected impedance follows from its square.

The RMS current the load draws. Zero is allowed and correctly gives zero power.
Leave blank to have it derived as Is ÷ n. Fill in both and any imbalance is flagged.
The impedance connected across the secondary — 8 Ω for a speaker.
Used to derive the currents when you have not typed either one.
100 % is the ideal model. Below that, the primary draws extra current and the difference is heat.

Secondary voltage V_s

12.000 V

Step-down19.167 : 1

V_s = V_p × N_s / N_p · ratio taken from the winding turns

More primary turns than secondary, so the voltage falls and the secondary current rises in the same proportion.

Ideal transformer assumed

The ideal model assumes perfect flux coupling, no winding resistance, no leakage inductance, no core loss and no magnetising current. A real transformer sags a few percent under load, so treat the ideal secondary voltage as the no-load figure and use the efficiency mode for the rest.

19.167 : 1

Np ÷ Ns, the number every other quantity is scaled by.

115 : 6

The same ratio with the common factor divided out, ready to wind.

0.200 V/turn

Vp ÷ Np — the same figure for both windings of one core.

Windings

Primary turns Np1150
Secondary turns Ns60
Primary voltage Vp230.000 V
Secondary voltage Vs12.000 V

Current, power and impedance

Primary current Ip260.870 mA
Secondary current Is5.000 A
Apparent power Sp60.000 VA
Apparent power Ss60.000 VA
Input power Pin60.000 W
Load impedance Zs8.000 Ω
Reflected impedance Zp = n²·Zs2.939 kΩ
corePrimaryVp = 230.000 VIp = 260.870 mANp = 1150SecondaryVs = 12.000 VIs = 5.000 ANs = 60Step-down — the winding drawn with more loops is the higher-voltage, lower-current side

Primary against secondary

TurnsNp = 1150Ns = 60VoltageVp = 230.000 VVs = 12.000 VCurrentIp = 260.870 mAIs = 5.000 A
StepWorking
Turns ration = N_p / N_s = 1150.000 / 60.000 = 19.167
Secondary voltageV_s = V_p × N_s / N_p = 230.000 V × 60.000 / 1150.000 = 12.000 V
Primary currentI_p = I_s / n = 5.000 A / 19.167 = 260.870 mA
Power balanceS_p = V_p·I_p = 60.000 VA, S_s = V_s·I_s = 60.000 VA
Reflected impedanceZ_p = n² × Z_s = 19.167² × 8.000 Ω = 2.939 kΩ
Volts per turnV/turn = V_p / N_p = 230.000 V / 1150.000 = 0.200 V/turn

Whole-turn options for the secondary

Half a turn cannot be wound, so these are the counts either side of the exact requirement and the voltage each one really delivers. Winders usually pick a turn or two above the ideal to make up for the volt drop under load.

Secondary turnsSecondary voltageError
5711.400 V-5.000 %
5811.600 V-3.333 %
5911.800 V-1.667 %
60 (nearest)12.000 V0.000 %
6112.200 V1.667 %
6212.400 V3.333 %
6312.600 V5.000 %

About This Tool

Transformer Turns Ratio Calculator – Voltage, Current and Impedance

A transformer is two windings sharing one magnetic core, and almost everything you need to know about it falls out of a single chain of equalities: n = N_p / N_s = V_p / V_s = I_s / I_p. This turns ratio calculator works that chain in every direction — give it any complete pair and it derives the rest, including the apparent power on both windings, the reflected impedance, the volts per turn and a realistic primary current once you tell it the efficiency.

What the turns ratio actually tells you

The ratio n is the number of primary turns divided by the number of secondary turns. When n > 1 the transformer is a step-down unit, when n < 1 it is a step-up unit, and when the windings are equal it is an isolation transformer whose whole purpose is the galvanic break rather than any change in voltage. A 1150-turn primary against a 60-turn secondary gives n = 19.167, which turns a 230 V mains supply into 230 / 19.167 = 12 V. Reduced to whole numbers that same winding is 115 : 6, and that pair is what a winder actually counts onto the bobbin.

Why current transforms the other way round

A transformer moves power, it does not create it, so the apparent power S = V × I is the same on both sides of an ideal unit. Dividing the voltage by 19.167 therefore multiplies the current by the same figure, which is why a 5 A load on that 12 V secondary draws only 5 / 19.167 = 0.261 A from the primary — and why the two windings check out at 60 VA each. It is also the reason step-down transformers are wound with thin wire on the many-turn primary and thick wire on the few-turn secondary.

Impedance matching squares the ratio

Impedance is voltage over current, and the transformer scales voltage by n while scaling current by 1/n, so impedance scales by . The reflected impedance seen looking into the primary is Z_p = n² · Z_s. That single squaring is what makes audio output transformers practical: matching a 5 kΩ valve plate load to an 8 Ω speaker needs a ratio of only √(5000 / 8) = 25 : 1. Run it the other way and the 19.167:1 mains winding above reflects an 8 Ω load as 2938.9 Ω.

The 4.44 in the EMF equation

V = 4.44 · f · N · B_max · A_c uses the conventional rounded form of 2π/√2 = 4.4429. Every winding table and datasheet quotes 4.44, so this calculator does too — the 0.07 % difference is far smaller than the spread in real core data.

Designing a core from scratch

The volts-per-turn mode runs the EMF equation forwards. At 50 Hz, with 6 cm² of core cross-section worked at a peak flux density of 1.2 T, each turn supports 0.1598 V. A 230 V primary is then 1439 turns and a 12 V secondary 75 turns. Because half a turn cannot be wound, the tool shows the exact requirement, the rounded winding, and the voltage that rounded winding really delivers, alongside a table of the nearby options. Push B_max much above 1.6 T in ordinary grain-oriented silicon steel and the core saturates: the magnetising current spikes, the core overheats, and the winding stops following the turns ratio at all.

From the ideal model to a real transformer

The ideal model assumes perfect coupling, no winding resistance, no leakage inductance and no core loss. Real units lose a few percent, so the efficiency mode takes the output power P_out = V_s · I_s, divides by η to get the input power, and reads the true primary current off that. The same 12 V, 5 A secondary at 95 % efficiency needs 63.16 W in rather than 60 W, pulls 0.275 A from the mains instead of 0.261 A, and dissipates the difference — 3.16 W — as heat in the copper and the core.

Units, checks and where the numbers land

Voltages are accepted in millivolts, volts and kilovolts; currents in microamps through kiloamps; impedances from milliohms to teraohms; core area in mm², cm², in² and more; flux density in tesla, millitesla and gauss. Everything is normalised to SI before the arithmetic and converted back only for display. If you over-specify the problem — supplying both windings and both voltages — and the two ratios disagree by more than half a percent, the tool names both figures instead of quietly preferring one, and it flags a power imbalance whenever the two currents you entered cannot both be true.

Frequently Asked Questions

Is the Transformer Turns Ratio Calculator free?

Yes, Transformer Turns Ratio Calculator is totally free :)

Can I use the Transformer Turns Ratio Calculator offline?

Yes, you can install the webapp as PWA.

Is it safe to use Transformer Turns Ratio Calculator?

Yes, any data related to Transformer Turns Ratio Calculator only stored in your browser (if storage required). You can simply clear browser cache to clear all the stored data. We do not store any data on server.

How does this transformer turns ratio calculator work?

It fixes the ratio n from whichever complete pair you supply — the two winding turns, the two winding voltages, the two currents, or a pair of impedances — and then derives everything else from that one unrounded number using n = N_p/N_s = V_p/V_s = I_s/I_p. A 1150-turn primary against a 60-turn secondary gives n = 19.167, so 230 V in becomes 12 V out and a 5 A load draws only 0.261 A from the mains. Nothing downstream is rebuilt from a value that has already been through a formatter.

Why does the current go the opposite way to the voltage?

Because a transformer moves power, it does not make it. The apparent power on each winding is V × I, and in the ideal model those two products are equal, so if the voltage is divided by 19.167 the current must be multiplied by the same 19.167 to keep the product fixed. That is why a step-down transformer has a thin, many-turn primary and a thick, few-turn secondary: the secondary is the side carrying the large current.

Why is the impedance ratio the square of the turns ratio?

Impedance is voltage divided by current, and the transformer scales voltage by n while scaling current by 1/n, so the quotient scales by n². That single squaring is what makes output transformers practical: matching a 5 kΩ valve plate load to an 8 Ω speaker needs Z_p/Z_s = 625, and √625 is only a 25:1 winding. The tool reports the reflected impedance Z_p = n²·Z_s whenever you give it a load, and solves the other way when you give it a target.

What is the 4.44 in the volts-per-turn equation?

It is the conventional rounded form of 2π/√2 = 4.4429 — the 2πf that converts a peak flux into a peak EMF, times the 1/√2 that converts that peak into the RMS value a voltmeter reads. Every winding table and datasheet quotes 4.44, so this calculator does too. With 50 Hz, a 6 cm² core and a peak flux density of 1.2 T you get 0.1598 V per turn, which makes a 230 V primary 1439 turns and a 12 V secondary 75 turns.

Why does the tool round the secondary turns, and does it matter?

Half a turn cannot be wound, so a design that asks for 75.075 turns has to become 75 or 76. The tool shows the exact requirement, the rounded winding and the voltage the rounded winding actually delivers, plus a table of the nearby whole-turn options with the error each one carries. In practice winders deliberately add a few turns to the secondary, because a real transformer sags a few percent under load and the ideal figure is the no-load value.

How close is this to a real transformer?

The arithmetic is exact for the numbers you enter, but the ideal model assumes perfect flux coupling, no winding resistance, no leakage inductance, no core loss and no magnetising current. A real unit shows a few percent of regulation from no load to full load, draws a magnetising current even with nothing connected, and saturates if the peak flux density goes much above 1.6 T in ordinary silicon steel. Use the efficiency mode for a realistic primary current and treat the ideal figures as the design starting point rather than a measurement.